FC series
Compliance to the following standards as per IEC61800-3:2011 has been met.
Phenomena |
Standard |
Test level |
Type of
environment |
Harmonics THD | IEC 61000-2-4 | 12% | 2nd |
All other harmonic orders As per table 24 | IEC 61000-4-13 class 3 | As per table 24 | 2nd |
Commutation notches | IEC 60146-1-1 Class B | Depth = 40 %, total area = 250 in % degrees | 2nd |
Voltage deviations (> 60 s) | IEC 61000-2-4 Class 2 | ± 10 % | 2nd |
Voltage dips | IEC 61000-4-11 Class 3 or IEC 61000-4-34 Class 3 |
As per Table 5 | 2nd |
Short interruptions | IEC 61000-4-11 Class 3 or IEC 61000-4-34 Class 3 |
Volts remaining 0%, Cycles 250/300 | 2nd |
ESD | IEC 61000-4-2 | 4 kV CD or 8 kV AD | 2nd |
Radio frequency electromagnetic field (AM) | IEC 61000-4-3 | As per table 12 IEC61800-3 | 2nd |
Fast Transient Burst | IEC 61000-4-4 | 2 kV/5 kHz(power ports) 1 kV/5 kHz Capacitive clamp (signal interface) |
2nd |
Surge 1,2/50 s, 8/20 s | IEC 61000-4-5 | 1 kV line to line 2 kV line to earth |
2nd |
Conducted radio frequency common mode | IEC 61000-4-6 | 0,15 MHz to 80 Mhz 10 V 80 % AM (1 kHz) – Power Ports 0,15 MHz to 80 MHz 10 V 80 % AM (1 kHz) – Signal interface |
2nd |
Compliance to IEC61800-5-1
Adjustable speed electrical power drive systems
Safety requirements – Electrical, thermal and energy